Question of the day / Oct 10, 2026
PE-level practice
Cooling-coil sensible load from standard-air 1.08
Oct 10, 2026 · America/New_York
HVACPE
A cooling coil sees 6,000 cfm. Entering dry-bulb is 80 °F and leaving dry-bulb is 55 °F. Using the standard-air sensible factor 1.08 Btu/h·cfm·°F, what is the sensible cooling rate?
Practice only — not PE exam credit, not an NCEES item, not a PE stamp, and not a substitute for licensed professional judgment or licensure. Original workbench questions for discussion. Verify against current codes and your own calculations. Terms