Check ASHRAE for glycol. The propylene-glycol fits are approximate, not for freeze-protection sizing, and ethylene glycol is not modelled.
The two inlets are inputs, so they are held by definition. Hold an outlet and something else has to move — pick what.
Equal multi-pass (1/1, 2/2, 3/3) is treated as overall counterflow — a teaching simplification with F≈1, not a full unequal-pass F correction.
Fouling allowances are hr·ft²·°F/Btu. A harder corrugation buys heat transfer and spends pressure drop; the port size and plate gap that go with each frame are in the table below.
| Duty | 0MBtu/hr · 0tons |
|---|---|
| Hot outlet | 0°F |
| Cold outlet | 0°F |
| Approach, hot end (Th,in − Tc,out) | 0°F |
| Approach, cold end (Th,out − Tc,in) | 0°F |
| LMTD | 0°F |
| Effectiveness ε · NTU | 0 · 0 |
| U, service (fouled) | 0Btu/hr·ft²·°F |
| Pressure drop, hot / cold | 0 / 0psi |
outlet temperature (°F)
| Effective plates (ends transfer nothing) | — |
|---|---|
| Channels per side, per pass | — |
| Heat transfer area | — |
| Channel gap / equivalent diameter | — |
| Flow path length (L × passes) | — |
| Port size / hot / cold port velocity | — |
| Overall U, clean | — |
| Overall U, service | — |
| Excess surface bought by the fouling allowance | — |
| Hot channel velocity / Reynolds | — |
|---|---|
| Cold channel velocity / Reynolds | — |
| Hot film coefficient | — |
| Cold film coefficient | — |
| Hot Prandtl / cold Prandtl | — |
| Plate wall resistance | — |
| Capacity rate ratio Cr | — |
| Hot pressure drop | — |
| Cold pressure drop | — |
Why holding an outlet needs something else to move. Five things go in — two inlet temperatures, two flows, and the surface — and two come out. An inlet is already an input, so holding one is just leaving the slider alone. An outlet is an answer, so pinning it removes a degree of freedom and one input has to give it back. Which input you pick is the whole engineering decision: moving the hot flow is a control valve, moving the plate count is a purchase, moving the hot inlet is a boiler or chiller reset. Hold both outlets and you have specified the duty itself — one flow follows from the energy balance and the plate count follows from the LMTD. That is the datasheet problem, and it is the one a sizing calculator actually solves.
Adding plates stops paying, and here is why. In a single-pass unit the same flow spread over more channels moves slower, so the film coefficient drops roughly as velocity0.7 while the area climbs linearly. You buy NTU at a worsening exchange rate and you lose the pressure drop that was doing the work. The honest lever for a close approach is a longer plate, a second pass, or a bigger frame — watch the pressure drop when you take the second pass, because it costs about six or seven times the first.
The approach is the number to argue about. A plate unit gets closer than a shell-and-tube because it is true counterflow, but a 2 °F approach and a 10 °F approach are different machines and different money. Both approaches are shown because the tight one moves to whichever end has the smaller capacity rate — unequal flows push the pinch to one end and leave surface idle at the other.
What is modelled and what is not. Rating is ε-NTU for pure counterflow, which is what a single-pass plate unit is. Equal multi-pass — the same pass count on both sides — is treated as overall counterflow, a teaching simplification with F≈1, not a full unequal-pass F correction. Film coefficients use calibrated chevron-family presets (C and K): Nu = C·Re0.70·Pr1/3 above Re 400 and blended to laminar slopes below it, with C and K set so a hard plate in water at Re 5000 lands near the published range for chevron plates — roughly 8000 W/m²·K and a few psi over a 36-inch plate. The Re 400 trip is a chevron-channel heuristic, not the pipe-flow transition at Re 2300, and the correlation is continuous there, so film coefficients drop sharply rather than discontinuously. These are not any manufacturer's plate curves. This is a teaching model: a real selection will not match it to better than 20 or 30 percent, and you should expect double-digit percent differences versus OEM software. Real plate data is proprietary and differs by pattern. Water properties are fitted over temperature except cp, which is held constant. Check ASHRAE for glycol. The propylene-glycol fits are approximate, not for freeze-protection sizing, and ethylene glycol is not modelled. Not modelled: the end-channel effect (the two outer channels only transfer on one face, which costs a little on small packs), flow maldistribution across the ports, unequal-pass F correction, gasket and frame pressure limits, and any two-phase duty.
An explanation tool, not a selection tool. Size real equipment with the manufacturer's software and a licensed engineer's judgment.